Z6_GHK6HJC0OG6S20Q8HU3K6R0G63
Z7_GHK6HJC0OG6S20Q8HU3K6R0GM5
Z7_GHK6HJC0OG6S20Q8HU3K6R0GM7
Z7_GHK6HJC0OG6S20Q8HU3K6R0Q22

S8610U3009/U HONEYWELL UNIVERSAL IGNITION MODULE

Item #: 84767 
Manufacturer Item: S8610U3009/U
Manufacturer: TCG - RESIDEO (HONEYWELL/ADEMC
24 VAC, Internal High Voltage Spark Generator, Natural Gas/Liquid Propane, Intermittent Pilot Ignition Module
84767

Universal Intermittent Pilot Ignition Module Replaces Multiple Field Installed Intermittent Pilot Modules

Uses Existing Intermittent Pilot Burner

Provides Ignition Sequencing, Flame Monitoring and Safety Shut-Off for Intermittent Pilot Warm Air Furnaces and Heating Appliances

Provides 100 Percent Pilot Gas Shut-Off if Pilot Fails to Light

After 6 Minute Delay, Trial for Ignition is Repeated

Ignition Trial/Delay Sequence is Repeated Until the Appliance Lights or Call for Heat is Removed

ignition components

Type
Universal
Application
Single Rod or Dual Rod/Remote Sense, Warm Air Furnace and He
Approval
CSA
Fuel Type
Natural Gas/Liquid Propane
Temperature Rating
-40 to 165 Deg F (Ambient)
Flame Sense Type
Single/Two Rod
Flame Failure Response Time
2 Second
Ignition Sequence
Continuous Retry
Ignition Source
Internal High Voltage Spark Generator
Ignition Trial Time
15 or 90 Second
Power Rating
24 Volt AC 60 Hertz
Pre-Purge Time
Configurable to 30 Second or No Pre-Purge
Valve Rating
1 Amp Pilot/2 Amp Main at 165 Deg F, 1 Amp Pilot/1 Amp Main